- Date
- 09/27/2021
- W/O
- 911340
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00639
- PipeID
- P13099
- Time
- 9:49 AM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9139
- Sewer Name
- 16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
- City
- SAN MARINO
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 14
- Purpose
- Routine Assessment
- Project
- RFIR_WO_911340_TV16121_SEP2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 12 in.
- Width
- 12 in.
- Upstream MH
- 16 0085
- Downstream MH
- 16 0084
- Dir. of Survey
- Downstream
- Length Surveyed
- 422.4 ft.
- Total Length
- 422.4 ft.
- Structural Index
- 3
- Structural Quick
- 3P2P
- Structural Rating
- 420
- O&M Index
- 2
- O&M Quick
- 2R1P
- O&M Rating
- 271
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 691
Pipe schematic from manhole 16 0085 to 16 0084 Observation photos (5)

2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

116.7 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start

155.4 ft. - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES

163.3 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES

168.2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start