Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2021, 08:27 AM
  • 16 0067_16 0066_09162021_013338.mp4

Date
09/16/2021
W/O
911340
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13081
Time
1:27 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9410
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_911340_TV16121_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0067
Downstream MH
16 0066
Dir. of Survey
Downstream
Length Surveyed
126.5 ft.
Total Length
126.5 ft.
Structural Index
3
Structural Quick
3D2D
Structural Rating
120
O&M Index
2
O&M Quick
2D00
O&M Rating
48
Overall Index
2
Overall Quick
Overall Rating
168
Pipe schematic from manhole 16 0067 to 16 0066
MH: 16 0067MH: 16 0066downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 00670 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start111 ft. MGO - General Observation - (1) RAT @ MH124 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish124 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish126.5 ft. AMH - Downstream Manhole, Survey Ends - 16 0066126.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish126.5 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWM
2DAGS
126.5AMH16 0066
126.5CM
2SSS
5.8CM
124DAGS
0AMH16 0067
0MWL
126.5MGOCONN @ MH 9 O'CLOCK/ACTIVE
124SSS
111MGO(1) RAT @ MH

Properties (7)

additional_info
630074091521202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-09-16T01:27:55-07:00
documentation
PROPIPE
is_lateral_inspection
false