Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2021, 08:28 AM
  • C 0287_C 0286_09282021_013952.mp4

Date
09/28/2021
W/O
911562
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00133
PipeID
P09747
Time
1:28 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9427
Sewer Name
C JOINT OUTFALL C - UNIT 6D
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
WO_911562_TV03130_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
27 in.
Upstream MH
C 0286
Downstream MH
C 0287
Dir. of Survey
Upstream
Length Surveyed
267.7 ft.
Total Length
267.7 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
45
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
45
Pipe schematic from manhole C 0286 to C 0287
MH: C 0286MH: C 0287upstream0 ft. AMH - Upstream Manhole, Survey Ends - C 028713.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish44.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start85.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"148.8 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES207.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.7 ft. MWL - Water Level, 20 %of cross sectional area267.7 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK267.7 ft. MWM - Water Mark, 35 %of cross sectional area267.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK267.7 ft. AMH - Downstream Manhole, Survey Begins - C 0286

Observation photos (2)

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    118.9 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    184.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
182.6TFC
184.3FL
60TFC
253.8FL
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWM
0MGOCONNECTION AT THE MH 9 OC'LOCK
0AMHC 0286
223.3TFC
118.9CM
267.7AMHC 0287

Properties (7)

additional_info
630074092721201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-09-28T01:28:59-07:00
documentation
PROPIPE
is_lateral_inspection
false