Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2021, 07:31 AM
  • C 0286_C 0285_09282021_005728.mp4

Date
09/28/2021
W/O
911562
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00133
PipeID
P09746
Time
12:31 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9427
Sewer Name
C JOINT OUTFALL C - UNIT 6D
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
WO_911562_TV03130_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
27 in.
Upstream MH
C 0285
Downstream MH
C 0286
Dir. of Survey
Upstream
Length Surveyed
374.4 ft.
Total Length
374.4 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole C 0285 to C 0286
MH: C 0285MH: C 0286upstream0 ft. AMH - Upstream Manhole, Survey Ends - C 02860 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK126.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"159 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.5 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES200.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES235.9 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES281.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"313.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"366.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"366.4 ft. RML - Roots Medium Lateral, at 02 o'clock, 15 %, within 8 inches of joint: NO374.4 ft. MWL - Water Level, 20 %of cross sectional area374.4 ft. AMH - Downstream Manhole, Survey Begins - C 0285374.4 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (3)

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    8 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    142.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    175.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
374.4AMHC 0286
138.5CL
374.4MGOCONNECTION AT THE MH 3 OC'LOCK
374.4MGOCONNECTION AT THE MH 9 OC'LOCK
93.3TF
0MWL
8TFA
8RML
142.9CL
175.9CL
60.8TF
174.3TF
215.4TF
0AMHC 0285
248TF
0MWM

Properties (7)

additional_info
630074092721201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-09-28T00:31:48-07:00
documentation
PROPIPE
is_lateral_inspection
false