Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2021, 05:39 AM
  • C 0283_C 0282_09272021_225605.mp4

Date
09/27/2021
W/O
911562
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00133
PipeID
P09743
Time
10:39 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9427
Sewer Name
C JOINT OUTFALL C - UNIT 6D
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
WO_911562_TV03130_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
27 in.
Upstream MH
C 0283
Downstream MH
C 0282
Dir. of Survey
Downstream
Length Surveyed
281.4 ft.
Total Length
281.4 ft.
Structural Index
3
Structural Quick
4135
Structural Rating
30
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
30
Pipe schematic from manhole C 0283 to C 0282
MH: C 0283MH: C 0282downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 02830 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area5.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES7.8 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES24.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES25.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.1 ft. CC - Crack Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES65.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES91.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES113.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES124.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.4 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES158.5 ft. FM - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES193.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES219.2 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES240.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES253.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.4 ft. AMH - Downstream Manhole, Survey Ends - C 0282

Observation photos (14)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    5.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    7.8 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    24.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    25.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES

    57.1 ft. - Crack Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    65.3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    106.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    113.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    151.4 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    158.5 ft. - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    203.7 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

    219.2 ft. - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    240.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    253.3 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (21)

DistanceCodeObservation
24.4CL
0AMHC 0283
0MWL
91.4TF
7.8CM
25.8TB
253.3TF
113.7CM
193.2TF
151.4CL
65.3CM
240.1CM
57.1CC
106.2CM
203.7CL
281.4AMHC 0282
219.2FC
124.4TF
5.4CL
0MWM
158.5FM

Properties (7)

additional_info
630074092721201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-09-27T22:39:01-07:00
documentation
PROPIPE
is_lateral_inspection
false