Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2021, 05:57 AM
  • C 0282_C 0281_09272021_231648.mp4

Date
09/27/2021
W/O
911562
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00133
PipeID
P09742
Time
10:57 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9427
Sewer Name
C JOINT OUTFALL C - UNIT 6D
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
WO_911562_TV03130_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
27 in.
Upstream MH
C 0282
Downstream MH
C 0281
Dir. of Survey
Downstream
Length Surveyed
251.9 ft.
Total Length
251.9 ft.
Structural Index
3
Structural Quick
3C21
Structural Rating
59
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
59
Pipe schematic from manhole C 0282 to C 0281
MH: C 0282MH: C 0281downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 02820 ft. MWM - Water Mark, 35 %of cross sectional area28.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"52.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"136 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES148.3 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES154.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES165.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start251.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK251.9 ft. AMH - Downstream Manhole, Survey Ends - C 0281251.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK251.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    110.1 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    136 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    148.3 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    156.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    165.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWL
52.9TF
154.5TF
251.9MGOCONNECTION AT THE MH 9 OC'LOCK
156.6CM
0AMHC 0282
148.3CM
110.1TF
0MWM
28.6TF
165.2CM
136CL
251.9AMHC 0281
251.9MGOCONNECTION AT THE MH 3 OC'LOCK
251.9CM

Properties (7)

additional_info
630074092721201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-09-27T22:57:52-07:00
documentation
PROPIPE
is_lateral_inspection
false