- Date
- 09/27/2021
- W/O
- 911562
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00133
- PipeID
- P09741
- Time
- 11:18 PM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9427
- Sewer Name
- C JOINT OUTFALL C - UNIT 6D
- City
- LAKEWOOD
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 03
- Page No.
- 13
- Purpose
- Routine Assessment
- Project
- WO_911562_TV03130_SEP2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 27 in.
- Upstream MH
- C 0281
- Downstream MH
- C 0487
- Dir. of Survey
- Downstream
- Length Surveyed
- 73.9 ft.
- Total Length
- 73.9 ft.
- Structural Index
- 4
- Structural Quick
- 4321
- Structural Rating
- 14
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole C 0281 to C 0487 Observation photos (4)

9.5 ft. - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES

13.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

21 ft. - Fracture Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

37.3 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES