Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2021, 09:21 AM
  • 05 2504_05 1098_09032021_023117.mp4

Date
09/03/2021
W/O
911335
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00488
PipeID
P06333
Time
2:21 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9349
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
WO_911335_TV05306_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
05 2504
Downstream MH
05 1098
Dir. of Survey
Downstream
Length Surveyed
309.6 ft.
Total Length
309.6 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole 05 2504 to 05 1098
MH: 05 2504MH: 05 1098downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MGO - General Observation - RAGS / OTHER @ 2 TO 3 O'CLK - U/S MH0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 25040 ft. MWL - Water Level, 35 %of cross sectional area5.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6" - TAP CAP HAS MULTIPLE CRACKS.120.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6" - LONGITUDINAL CRACK ACROSS TAP CAP.220 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"309.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1098

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
5.9CM
0MGOCONNECTION AT THE MH 9 OC'LOCK
220TFC
0MGORAGS / OTHER @ 2 TO 3 O'CLK - U/S MH
0MGOCONNECTION AT THE MH 3 OC'LOCK
120.5TFCLONGITUDINAL CRACK ACROSS TAP CAP.
43.2TFCTAP CAP HAS MULTIPLE CRACKS.
0MWM
309.6CM
0AMH05 2504
309.6AMH05 1098
0MWL

Properties (7)

additional_info
630074090221202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-09-03T02:21:35-07:00
documentation
PROPIPE
is_lateral_inspection
false