Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2021, 09:41 AM
  • 05 1097_05 1096_09032021_025124.mp4

Date
09/03/2021
W/O
911335
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00488
PipeID
P06331
Time
2:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9349
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
WO_911335_TV05306_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
05 1097
Downstream MH
05 1096
Dir. of Survey
Downstream
Length Surveyed
321.3 ft.
Total Length
321.3 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
189
Pipe schematic from manhole 05 1097 to 05 1096
MH: 05 1097MH: 05 1096downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 10974.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start87.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"187.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"288.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6" - CAP HAS LONGITUDINAL CRACK ON FACE.321.3 ft. MGO - General Observation - ACTIVE CONNECTION AT THE MH 9 OC'LOCK321.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1096

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWL
321.3MGOACTIVE CONNECTION AT THE MH 9 OC'LOCK
187.9TFC
0MWM
4.2CM
321.3CM
288.5TFCCAP HAS LONGITUDINAL CRACK ON FACE.
321.3AMH05 1096
87.8TFC
0AMH05 1097

Properties (7)

additional_info
630074090221202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-09-03T02:41:38-07:00
documentation
PROPIPE
is_lateral_inspection
false