Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2021, 08:56 AM
  • 05 2494_05 1091_09142021_021519.mp4

Date
09/14/2021
W/O
911335
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00488
PipeID
P06326
Time
1:56 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9406
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
WO_911335_TV05306_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
15 in.
Upstream MH
05 1091
Downstream MH
05 2494
Dir. of Survey
Upstream
Length Surveyed
421.2 ft.
Total Length
421.2 ft.
Structural Index
3
Structural Quick
4B3C
Structural Rating
128
O&M Index
2
O&M Quick
2T00
O&M Rating
208
Overall Index
2
Overall Quick
Overall Rating
336
Pipe schematic from manhole 05 1091 to 05 2494
MH: 05 1091MH: 05 2494upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 24940.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish0.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish0.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK101.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start101.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start101.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish116.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start120.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"125.9 ft. MGO - General Observation - APPROXIMATELY A 5" GAP IN JOINT SEAL @ APPROX. 2 O'CLOCK175.1 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Finish220.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - TAP APPEARS BROKEN INTERNALLY247 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start247 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Finish253.6 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start320.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"419.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start421.2 ft. MGO - General Observation - ACTIVE CONNECTION AT THE MH 9 O' CLOCK421.2 ft. AMH - Downstream Manhole, Survey Begins - 05 1091421.2 ft. MWL - Water Level, 20 %of cross sectional area421.2 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start

    167.6 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start

    174.2 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    305.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    319.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
319.7DSZ
0MGOACTIVE CONNECTION AT THE MH 9 O' CLOCK
420.5FL
295.3MGOAPPROXIMATELY A 5" GAP IN JOINT SEAL @ APPROX. 2 O'CLOCK
301.1TFC
305.1CL
2.1DAGS
174.2FM
319.7FL
420.5DSZ
174.2CM
420.5DAGS
420.5MGOCONNECTION AT THE MH 9 OC'LOCK
101.1TFC
201.1TFATAP APPEARS BROKEN INTERNALLY
421.2AMH05 2494
319.7CL
0AMH05 1091
0MWL
246.1FM
0MWM
167.6CM

Properties (7)

additional_info
630074091321202
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-14T01:56:54-07:00
documentation
PROPIPE
is_lateral_inspection
false