Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2021, 09:10 AM
  • E 0126_G 0094_09102021_021524.mp4

Date
09/10/2021
W/O
911507
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00027
PipeID
P07608
Time
2:10 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9358
Sewer Name
E JOINT OUTFALL E - UNIT 1
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_911507_TV30070_SEP2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
15 in.
Upstream MH
E 0126
Downstream MH
G 0094
Dir. of Survey
Downstream
Length Surveyed
17.7 ft.
Total Length
17.7 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
16
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
20
Pipe schematic from manhole E 0126 to G 0094
MH: E 0126MH: G 0094downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - E 01260 ft. MWM - Water Mark, 50 %of cross sectional area5.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start5.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start16.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish16.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish16.1 ft. MGO - General Observation - STOP LOG (DAMAGED / MODIFIED STOP LOG?) CONNECTION AT MH 12 O'CLOCK17.7 ft. AMH - Downstream Manhole, Survey Ends - G 0094

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • General Observation - STOP LOG (DAMAGED / MODIFIED STOP LOG?) CONNECTION AT MH 12 O'CLOCK

    16.1 ft. - General Observation - STOP LOG (DAMAGED / MODIFIED STOP LOG?) CONNECTION AT MH 12 O'CLOCK

Observations (10)

DistanceCodeObservation
5.6SAP
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
16.1SAP
5.6SRV
17.7AMHG 0094
0AMHE 0126
0MWM
16.1SRV
16.1MGOSTOP LOG (DAMAGED / MODIFIED STOP LOG?) CONNECTION AT MH 12 O'CLOCK

Properties (7)

additional_info
630069090921203
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-09-10T02:10:31-07:00
documentation
PRO PIPE
is_lateral_inspection
false