Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2021, 08:53 AM
  • 16 0013_16 0012_09212021_015547.mp4

Date
09/21/2021
W/O
911302
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13049
Time
1:53 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9418
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN GABRIEL
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_911302_TV16107_SEP2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
16 0013
Downstream MH
16 0012
Dir. of Survey
Downstream
Length Surveyed
19 ft.
Total Length
19 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 16 0013 to 16 0012
MH: 16 0013MH: 16 0012downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 00132.6 ft. MGO - General Observation - MAG COAT2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish19 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK19 ft. AMH - Downstream Manhole, Survey Ends - 16 0012

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
19SAP
19MGOCONNECTION AT THE MH 3 OC'LOCK
2.6MGOMAG COAT
0MWM
2.6SAP
0MWL
19AMH16 0012
0AMH16 0013

Properties (7)

additional_info
630074092021203
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2021-09-21T01:53:00-07:00
documentation
PROPIPE
is_lateral_inspection
false