Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2021, 06:21 AM
  • C 0102A_C 0102_09292021_000804.mp4

Date
09/28/2021
W/O
911347
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00123
PipeID
P09570
Time
11:21 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9431
Sewer Name
C JOINT OUTFALL C - UNIT 3D
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_911347_TV03156_SEP2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
30 in.
Upstream MH
C 0102A
Downstream MH
C 0102
Dir. of Survey
Downstream
Length Surveyed
349.6 ft.
Total Length
349.6 ft.
Structural Index
3
Structural Quick
5M3M
Structural Rating
690
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
690
Pipe schematic from manhole C 0102A to C 0102
MH: C 0102AMH: C 0102downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 0102A0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.1 ft. HVV - Hole Void Visible, at 02 o'clock, within 8 inches of joint: YES349.6 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED349.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349.6 ft. AMH - Downstream Manhole, Survey Ends - C 0102

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole Void Visible, at 02 o'clock, within 8 inches of joint: YES

    8.1 ft. - Hole Void Visible, at 02 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
2.9SSS
0MWM
349.6MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
349.6SSS
8.1SRV
0MWL
349.6SRV
8.1HVV
349.6SAP
0AMHC 0102A
2.9SAP
0MGOCONNECTION AT THE MH 9 OC'LOCK
349.6AMHC 0102

Properties (7)

additional_info
630074092821203
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-09-28T23:21:48-07:00
documentation
PROPIPE
is_lateral_inspection
false