Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 16, 2021, 07:59 AM
  • 16 0069_16 0068_09162021_010358.mp4

Date
09/16/2021
W/O
911345
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13083
Time
12:59 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9409
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_911345_TV16004_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0069
Downstream MH
16 0068
Dir. of Survey
Downstream
Length Surveyed
61.9 ft.
Total Length
61.9 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
55
O&M Index
2
O&M Quick
2A00
O&M Rating
22
Overall Index
2
Overall Quick
Overall Rating
77
Pipe schematic from manhole 16 0069 to 16 0068
MH: 16 0069MH: 16 0068downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 00692 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start59 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish59 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish61.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish61.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE61.9 ft. AMH - Downstream Manhole, Survey Ends - 16 0068

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
61.9AMH16 0068
61.8MGOCONN @ MH 9 O'CLOCK/ACTIVE
2CM
61.5CM
0MWM
2SSS
59SSS
2DAGS
0AMH16 0069
59DAGS

Properties (7)

additional_info
630074091521201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-09-16T00:59:33-07:00
documentation
PROPIPE
is_lateral_inspection
false