Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2021, 04:30 AM
  • 16 0064_16 0063_09162021_041213.mp4

Date
09/16/2021
W/O
911345
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13078
Time
9:30 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9411
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_911345_TV16004_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0064
Downstream MH
16 0063
Dir. of Survey
Downstream
Length Surveyed
386.7 ft.
Total Length
386.7 ft.
Structural Index
3
Structural Quick
423O
Structural Rating
398
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
550
Pipe schematic from manhole 16 0064 to 16 0063
MH: 16 0064MH: 16 0063downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 00640 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.5 ft. CS - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES26.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES74.3 ft. FM - Fracture Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES76.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"100.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN171.3 ft. FM - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES217.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES357.8 ft. TB - Tap Break-In, at 10 o'clock, within 8 inches of joint: NO, 6" - OPEN375.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"384 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish384 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0063

Observation photos (10)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    8.5 ft. - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    26.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    74.3 ft. - Fracture Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"

    76.2 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    100.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    171.3 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    217.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, within 8 inches of joint: NO, 6" - OPEN

    357.8 ft. - Tap Break-In, at 10 o'clock, within 8 inches of joint: NO, 6" - OPEN

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"

    375.7 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"

Observations (19)

DistanceCodeObservation
217.8CM
0AMH16 0064
74.3FM
0MWL
386.6CM
375.7TBA
171.3FM
2DAGS
0MWM
100.8TBOPEN
384DAGS
2SSS
2CM
8.5CS
76.2TBA
386.7AMH16 0063
357.8TBOPEN
26.1CL
384SSS

Properties (7)

additional_info
630074091621201
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-16T21:30:00-07:00
documentation
PROPIPE
is_lateral_inspection
false