Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2021, 06:31 AM
  • 16 0060_16 0059_09162021_234502.mp4

Date
09/16/2021
W/O
911345
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13073
Time
11:31 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9411
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_911345_TV16004_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0060
Downstream MH
16 0059
Dir. of Survey
Downstream
Length Surveyed
375.4 ft.
Total Length
375.4 ft.
Structural Index
3
Structural Quick
413N
Structural Rating
377
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
525
Pipe schematic from manhole 16 0060 to 16 0059
MH: 16 0060MH: 16 0059downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 00602 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start154.2 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES373 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish373 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish375 ft. MGO - General Observation - ROACHES @ MH375.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish375.4 ft. AMH - Downstream Manhole, Survey Ends - 16 0059

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    154.2 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
373SSS
2DAGS
2SSS
375MGOROACHES @ MH
2CM
373DAGS
0MWL
0MWM
375.4CM
375.4AMH16 0059
0AMH16 0060
154.2FM

Properties (7)

additional_info
630074091621201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-09-16T23:31:06-07:00
documentation
PROPIPE
is_lateral_inspection
false