Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2021, 07:15 AM
  • 21 0901_21 0900_09152021_003309.mp4

Date
09/15/2021
W/O
911529
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00775
PipeID
P15976
Time
12:15 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9363
Sewer Name
21 LA VERNE-"B" STREET TRUNK
City
LA VERNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_911529_TV21054_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
21 0901
Downstream MH
21 0900
Dir. of Survey
Downstream
Length Surveyed
395.1 ft.
Total Length
395.1 ft.
Structural Index
3
Structural Quick
423O
Structural Rating
401
O&M Index
2
O&M Quick
2O00
O&M Rating
156
Overall Index
2
Overall Quick
Overall Rating
557
Pipe schematic from manhole 21 0901 to 21 0900
MH: 21 0901MH: 21 0900downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 09012 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES41.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.8 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES, Start201.8 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES, Finish243.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"391.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish393 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish393.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish395.1 ft. AMH - Downstream Manhole, Survey Ends - 21 0900

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    5.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES, Start

    198.8 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
393.4DAGS
393SSS
5.5CM
2DAGS
198.8FM
391.5CM
201.8FM
192.7TFC
2CM
41.8TFC
0MWM
2SSS
243.2TFC
92.4TFC
395.1AMH21 0900
0MWL
0AMH21 0901
143TFC

Properties (7)

additional_info
630069091421201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-09-15T00:15:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false