Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2021, 06:47 AM
  • 14 0114_14 0740_09232021_000123.mp4

Date
09/22/2021
W/O
911393
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00571
PipeID
P18144
Time
11:47 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9374
Sewer Name
14 DISTRICT #14 OUTFALL TRUNK
City
LANCASTER
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_911393_TV14075_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0114
Downstream MH
14 0740
Dir. of Survey
Downstream
Length Surveyed
280.5 ft.
Total Length
280.5 ft.
Structural Index
4
Structural Quick
4H3A
Structural Rating
208
O&M Index
2
O&M Quick
2J00
O&M Rating
110
Overall Index
3
Overall Quick
Overall Rating
318
Pipe schematic from manhole 14 0114 to 14 0740
MH: 14 0114MH: 14 0740downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 01140 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start9.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start63.9 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES67.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish67.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start74.5 ft. RPZ - Repair Other, within 8 inches of joint: YES - POSSIBLE REPAIR/ABANDONED STRUCTURE74.5 ft. MGP - General Photograph - POSSIBLE REPAIR/ABANDONED STRUCTURE278.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish278.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0740, RUN LIST STATES MH AT 318'.

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    63.9 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    67.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES - POSSIBLE REPAIR/ABANDONED STRUCTURE

    74.5 ft. - Repair Other, within 8 inches of joint: YES - POSSIBLE REPAIR/ABANDONED STRUCTURE

  • General Photograph - POSSIBLE REPAIR/ABANDONED STRUCTURE

    74.5 ft. - General Photograph - POSSIBLE REPAIR/ABANDONED STRUCTURE

Observations (13)

DistanceCodeObservation
280.5AMH14 0740, RUN LIST STATES MH AT 318'.
74.5RPZPOSSIBLE REPAIR/ABANDONED STRUCTURE
67.4CM
67.4FM
74.5MGPPOSSIBLE REPAIR/ABANDONED STRUCTURE
63.9FM
9.7CM
0MWL
278.3DAGS
278.3FM
2DAGS
0AMH14 0114
0MWM

Properties (7)

additional_info
630069092221201
custom_field_three
FRACTURES/CRACKS
custom_field_two
2
customer
1
datetime
2021-09-22T23:47:41-07:00
documentation
PRO PIPE
is_lateral_inspection
false