Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 20, 2021, 11:42 AM
  • 32 0119A_32 0119_09202021_044715.mp4

Date
09/20/2021
W/O
911391
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19865
Time
4:42 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9371
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_911391_TV32048_SEP2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
32 0119
Downstream MH
32 0119A
Dir. of Survey
Upstream
Length Surveyed
45.8 ft.
Total Length
45.8 ft.
Structural Index
3
Structural Quick
3800
Structural Rating
24
O&M Index
2
O&M Quick
2800
O&M Rating
16
Overall Index
3
Overall Quick
Overall Rating
40
Pipe schematic from manhole 32 0119 to 32 0119A
MH: 32 0119MH: 32 0119Aupstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 32 0119A2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish39.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start43.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start45.8 ft. MWM - Water Mark, 10 %of cross sectional area45.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE45.8 ft. MWL - Water Level, 10 %of cross sectional area45.8 ft. AMH - Downstream Manhole, Survey Begins - 32 0119

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    45.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
43.8SAV
45.8MGOCONNECTION AT MH 3 O'CLOCK
43.8DAGS
2DAGS
5.9SAV
45.8MGOCOCKROACHES IN MANHOLE
0MWM
45.8AMH32 0119A
0MGOCOCKROACHES IN MANHOLE
0MWL
0AMH32 0119

Properties (7)

additional_info
630069092021002
custom_field_three
VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2021-09-20T04:42:01-07:00
documentation
PRO PIPE
is_lateral_inspection