Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 20, 2021, 11:33 AM
  • 32 0119_32 0118_09202021_043934.mp4

Date
09/20/2021
W/O
911391
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19864
Time
4:33 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9371
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_911391_TV32048_SEP2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
32 0118
Downstream MH
32 0119
Dir. of Survey
Upstream
Length Surveyed
75.8 ft.
Total Length
75.8 ft.
Structural Index
4
Structural Quick
563B
Structural Rating
72
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
72
Pipe schematic from manhole 32 0118 to 32 0119
MH: 32 0118MH: 32 0119upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 32 01192.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish42.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish73.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start73.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start75.8 ft. MWL - Water Level, 10 %of cross sectional area75.8 ft. MWM - Water Mark, 10 %of cross sectional area75.8 ft. AMH - Downstream Manhole, Survey Begins - 32 0118

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    75.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (9)

DistanceCodeObservation
75.8MGOCOCKROACHES IN MANHOLE
0MWL
2SAP
0MWM
75.8AMH32 0119
2SRV
73.6SAP
33.2SRV
0AMH32 0118

Properties (7)

additional_info
630069092021002
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-09-20T04:33:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false