Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2021, 05:34 AM
  • 32 0138_32 0137A_09202021_224358.mp4

Date
09/20/2021
W/O
911391
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00887
PipeID
P19886
Time
10:34 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9372
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_911391_TV32048_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0138
Downstream MH
32 0137A
Dir. of Survey
Downstream
Length Surveyed
246.6 ft.
Total Length
246.6 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
147
O&M Index
2
O&M Quick
2I00
O&M Rating
98
Overall Index
3
Overall Quick
Overall Rating
245
Pipe schematic from manhole 32 0138 to 32 0137A
MH: 32 0138MH: 32 0137Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 01380 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start244.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish244.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish246.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK246.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE246.6 ft. AMH - Downstream Manhole, Survey Ends - 32 0137A

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    246.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
244.6SAP
0AMH32 0138
0MWM
2DAGS
246.6MGOCONNECTION AT MH 9 O'CLOCK
0MWL
244.6DAGS
2SAP
246.6MGOCOCKROACHES IN MANHOLE
246.6AMH32 0137A

Properties (7)

additional_info
630069092021201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-09-20T22:34:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false