Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2021, 05:24 AM
  • 08 0330_08 0329_09072021_223800.mp4

Date
09/07/2021
W/O
911693
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00013
PipeID
P00379
Time
10:24 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9350
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_911693_TV08155_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0329
Downstream MH
08 0330
Dir. of Survey
Upstream
Length Surveyed
335.2 ft.
Total Length
335.2 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
164
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
164
Pipe schematic from manhole 08 0329 to 08 0330
MH: 08 0329MH: 08 0330upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 03300.1 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK0.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish87.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"200.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start274.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES287.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"335.2 ft. MWM - Water Mark, 10 %of cross sectional area335.2 ft. AMH - Downstream Manhole, Survey Begins - 08 0329335.2 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    61.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    67.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWM
248.1TFC
61.1CL
0AMH08 0329
335.2AMH08 0330
335.1MGOCONNECTION AT THE MH 12 OC'LOCK
0MWL
67.1CM
152.1TFC
200.4TFC
335.1MGOCONNECTION AT THE MH 9 OC'LOCK
335.1CM
47.6TFC
98.6TFC
134.5TF

Properties (7)

additional_info
630074090721201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-09-07T22:24:55-07:00
documentation
PROPIPE
is_lateral_inspection
false