Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2021, 09:49 AM
  • 08 0308_08 0307_09132021_030225.mp4

Date
09/13/2021
W/O
911693
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00013
PipeID
P00354
Time
2:49 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9403
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_911693_TV08155_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
08 0308
Downstream MH
08 0307
Dir. of Survey
Downstream
Length Surveyed
313.2 ft.
Total Length
313.2 ft.
Structural Index
4
Structural Quick
4K00
Structural Rating
248
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
248
Pipe schematic from manhole 08 0308 to 08 0307
MH: 08 0308MH: 08 0307downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03080 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK4.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"82.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"132.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"183.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"234 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"282.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"313.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0307313.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish313.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
4.4FM
234TFC
313.2AMH08 0307
34.4TFC
0MWL
132.6TFC
82.8TFC
313.2FM
183.5TF
0MWM
313.2MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
0AMH08 0308
282.2TFC
0MGOCONNECTION AT THE MH 3 OC'LOCK

Properties (7)

additional_info
630074091321002
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-13T02:49:19-07:00
documentation
PROPIPE
is_lateral_inspection
false