Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2021, 10:02 AM
  • 08 0307_08 0306_09132021_030855.mp4

Date
09/13/2021
W/O
911693
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00013
PipeID
P00353
Time
3:02 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9403
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_911693_TV08155_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
08 0307
Downstream MH
08 0306
Dir. of Survey
Downstream
Length Surveyed
80.2 ft.
Total Length
80.2 ft.
Structural Index
4
Structural Quick
4B33
Structural Rating
61
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
61
Pipe schematic from manhole 08 0307 to 08 0306
MH: 08 0307MH: 08 0306downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03074.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"80.2 ft. AMH - Downstream Manhole, Survey Ends - 08 030680.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK80.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
16.9FM
0MWM
20.6TFC
0MWL
0AMH08 0307
16.9CM
80.2AMH08 0306
80.2MGOCONNECTION AT THE MH 3 OC'LOCK
80.2FM
4.2CM

Properties (7)

additional_info
630074091321002
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-13T03:02:58-07:00
documentation
PROPIPE
is_lateral_inspection
false