Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2021, 10:45 AM
  • 02 1340A_02 1340_08302021_035925.mp4

Date
08/30/2021
W/O
911863
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03865
Time
3:45 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9339
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_911863_TV02024_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 1340A
Downstream MH
02 1340
Dir. of Survey
Downstream
Length Surveyed
325.7 ft.
Total Length
325.7 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
320
O&M Index
2
O&M Quick
2900
O&M Rating
18
Overall Index
2
Overall Quick
Overall Rating
338
Pipe schematic from manhole 02 1340A to 02 1340
MH: 02 1340AMH: 02 1340downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 1340A0 ft. MWL - Water Level, 30% %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40 ft. MWL - Water Level, 20 %of cross sectional area47.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish66.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN132.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN196 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN323 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.7 ft. MGO - General Observation - ROACHES @ MH325.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1340325.7 ft. MGO - General Observation - POSSIBLE DROP CONN @ MH 12 O'CLOCK/ACTIVE325.7 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (2)

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    4 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
325.7SAV
132.8TFOPEN
47.2DSZ
325.7MGOROACHES @ MH
0AMH02 1340A
4DSZ
40MWL
0MWL
196TFOPEN
66.6TFOPEN
2SSS
323SSS
325.7AMH02 1340
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
325.7MGOPOSSIBLE DROP CONN @ MH 12 O'CLOCK/ACTIVE
4SAV
325.7MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWM

Properties (7)

additional_info
630074083021002
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-08-30T03:45:58-07:00
documentation
PROPIPE
is_lateral_inspection
false