Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2021, 06:04 AM
  • 02 1332_02 1331_08302021_231213.mp4

Date
08/30/2021
W/O
911863
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03856
Time
11:04 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9340
Sewer Name
02 BELVEDERE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_911863_TV02024_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
27 in.
Upstream MH
02 1332
Downstream MH
02 1331
Dir. of Survey
Downstream
Length Surveyed
159.1 ft.
Total Length
159.1 ft.
Structural Index
3
Structural Quick
3M22
Structural Rating
214
O&M Index
2
O&M Quick
2E00
O&M Rating
62
Overall Index
3
Overall Quick
Overall Rating
276
Pipe schematic from manhole 02 1332 to 02 1331
MH: 02 1332MH: 02 1331downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13320 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"23.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"24 ft. MWL - Water Level, 20 %of cross sectional area34.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start40.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN72 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN72 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish104.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN157 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish157 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish157 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish159 ft. MGO - General Observation - ROACHES @ MH159.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1331159.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE159.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish159.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    34.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (25)

DistanceCodeObservation
3.7SAV
159.1AMH02 1331
23.2TFC
104.1TFOPEN
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
2SSS
0MWL
2DAGS
159.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
0AMH02 1332
24MWL
34.4FL
159.1SAV
14.3TFC
157CM
72TFOPEN
159MGOROACHES @ MH
2CM
40.1TFOPEN
72FL
157DAGS
0MGOROACHES @ MH
0MWM
159.1MGOCONN @ MH 9 O'CLOCK/CAPPED
157SSS

Properties (7)

additional_info
630074083021201
custom_field_three
AGGREGATE VISIBLE/SPALLING
custom_field_two
3
customer
1
datetime
2021-08-30T23:04:27-07:00
documentation
PROPIPE
is_lateral_inspection
false