Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2021, 06:56 AM
  • B 0714_B 0713_09022021_001415.mp4

Date
09/01/2021
W/O
911654
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00110
PipeID
P09387
Time
11:56 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9118
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_911654_TV15057_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
39 in.
Upstream MH
B 0713
Downstream MH
B 0714
Dir. of Survey
Upstream
Length Surveyed
330 ft.
Total Length
330 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole B 0713 to B 0714
MH: B 0713MH: B 0714upstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 2 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - B 07140.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish98.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"152.6 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"201 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"203.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"249.9 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"252.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"300 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"303.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"303.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start328 ft. MGO - General Observation - MAG COATING THROUGHOUT330 ft. MWM - Water Mark, 30 %of cross sectional area330 ft. MWL - Water Level, 10 %of cross sectional area330 ft. AMH - Downstream Manhole, Survey Begins - B 0713

Observation photos (3)

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    26.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    80.1 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

Observations (19)

DistanceCodeObservation
329.9SAV
330MGOCONNECTION AT MH 3 O'CLOCK
0MWM
30TFC
26.1TF
77.9TF
2MGOMAG COATING THROUGHOUT
0MWL
26.1SAV
231.6TFC
330MGOCONNECTION AT MH 2 O'CLOCK
0AMHB 0713
330AMHB 0714
177.4TFA
80.1TB
228.8TFC
180.6TFC
126.5TF
129TFC

Properties (7)

additional_info
630069090121201
custom_field_three
AGGREGATE VISIBLE, MAG COAT
custom_field_two
3
customer
1
datetime
2021-09-01T23:56:44-07:00
documentation
PRO PIPE
is_lateral_inspection
false