Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2021, 06:06 AM
  • B 0710_B 0709_09012021_231910.mp4

Date
09/01/2021
W/O
911654
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00110
PipeID
P09383
Time
11:06 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9118
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_911654_TV15057_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
39 in.
Upstream MH
B 0710
Downstream MH
B 0709
Dir. of Survey
Downstream
Length Surveyed
251.6 ft.
Total Length
251.6 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
150
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
150
Pipe schematic from manhole B 0710 to B 0709
MH: B 0710MH: B 0709downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07100 ft. MWL - Water Level, 15 %of cross sectional area2.2 ft. MGO - General Observation - MAG COATING THROUGHOUT2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"61 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"63.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"106 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.1 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"160 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"250 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish251.6 ft. AMH - Downstream Manhole, Survey Ends - B 0709251.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • General Observation - MAG COATING THROUGHOUT

    2.2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    63.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    112.1 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
106TFC
250SAV
61TFC
0MGOCONNECTION AT MH 3 O'CLOCK
220.8TFC
251.6AMHB 0709
251.6MGOCONNECTION AT MH 3 O'CLOCK
0MWM
0AMHB 0710
63.8TB
0MWL
160TFC
2.2MGOMAG COATING THROUGHOUT
2.2SAV
9TFC
112.1TB

Properties (7)

additional_info
630069090121201
custom_field_three
AGGREGATE VISIBLE, MAG COAT
custom_field_two
3
customer
1
datetime
2021-09-01T23:06:03-07:00
documentation
PRO PIPE
is_lateral_inspection
false