Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2021, 08:21 AM
  • 01 0207_01 0206_09132021_013824.mp4

Date
09/13/2021
W/O
911861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01249
Time
1:21 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9402
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_911861_TV01011_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0207
Downstream MH
01 0206
Dir. of Survey
Downstream
Length Surveyed
349.8 ft.
Total Length
349.8 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
212
Pipe schematic from manhole 01 0207 to 01 0206
MH: 01 0207MH: 01 0206downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02070 ft. MWL - Water Level, 10 %of cross sectional area2.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"54.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"105.8 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6" - POSSIBLE ROOTS IN CONNECTION111.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6"149.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"218.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"272.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"275.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"304.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES326.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"349.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK349.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0206349.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    304.4 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
131.4TFA
349.8MGOCONNECTION AT THE MH 9 OC'LOCK
349.8AMH01 0206
275.2TF
326.2TFA
111.3TF
218.4TF
54.6TF
149.3TF
304.4FL
205.9TFA
0MWM
2.7SAV
39.4TF
0AMH01 0207
0MWL
105.8TFDPOSSIBLE ROOTS IN CONNECTION
349.8SAV
272.8TF
267.5TFA

Properties (7)

additional_info
630074091321001
custom_field_three
AGGREGATE VISIBLE/FRACTURES
custom_field_two
3
customer
1
datetime
2021-09-13T01:21:04-07:00
documentation
PROPIPE
is_lateral_inspection
false