Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2021, 04:17 AM
  • 01 0227_01 0226_09022021_213456.mp4

Date
09/02/2021
W/O
911861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01269
Time
9:17 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9348
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_911861_TV01011_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
15 in.
Upstream MH
01 0227
Downstream MH
01 0226
Dir. of Survey
Downstream
Length Surveyed
303.4 ft.
Total Length
303.4 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole 01 0227 to 01 0226
MH: 01 0227MH: 01 0226downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02270.1 ft. MWM - Water Mark, 25 %of cross sectional area2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"118 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"184.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"233.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES297.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0226303.4 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK303.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    233.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
297.5TF
34.8TF
224.1TF
88.4TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
148.2TF
72.9TF
118TF
303.4AMH01 0226
0MWL
2.2SAV
194.4TF
0.1MWM
303.4MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH01 0227
61.1TF
303.4SAV
171.6TF
176.9TF
184.6TF
110.3TF
233.8FL

Properties (7)

additional_info
630074090221201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-09-02T21:17:58-07:00
documentation
PROPIPE
is_lateral_inspection
false