Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2021, 06:42 AM
  • 01 0220_01 0219_09012021_235551.mp4

Date
09/01/2021
W/O
911861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01262
Time
11:42 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9346
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_911861_TV01011_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0220
Downstream MH
01 0219
Dir. of Survey
Downstream
Length Surveyed
286.5 ft.
Total Length
286.5 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
171
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
171
Pipe schematic from manhole 01 0220 to 01 0219
MH: 01 0220MH: 01 0219downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02200 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"138.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"181.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"189 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"286.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK286.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish286.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0219

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
286.5MGOCONNECTION AT THE MH 9 OC'LOCK
286.5SAV
221.8TF
140.8TF
138.6TF
65.2TF
0MWM
2.5SAV
0AMH01 0220
286.5AMH01 0219
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
100.9TF
189TF
39.8TF
88.1TF
181.6TF
257.7TF
234.8TF

Properties (7)

additional_info
630074090121201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-09-01T23:42:34-07:00
documentation
PROPIPE
is_lateral_inspection
false