Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2021, 06:30 AM
  • 01 0218_01 0217_09022021_234328.mp4

Date
09/02/2021
W/O
911861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01260
Time
11:30 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9348
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_911861_TV01011_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Square
Height
12 in.
Width
15 in.
Upstream MH
01 0218
Downstream MH
01 0217
Dir. of Survey
Downstream
Length Surveyed
325.5 ft.
Total Length
325.5 ft.
Structural Index
3
Structural Quick
423X
Structural Rating
380
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
380
Pipe schematic from manhole 01 0218 to 01 0217
MH: 01 0218MH: 01 0217downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02182.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.7 ft. FM - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES31.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start48.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"51.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"68 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES71.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"190 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"218 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"235.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"240.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0217325.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

    2.7 ft. - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    31.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    68 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
88.2TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
240.4TF
2.7SAV
48.3TF
0MWL
298.7TF
325.5CM
167.2TF
31.1CM
191.2TF
325.5SAV
68FM
51.6TF
325.5AMH01 0217
2.7FM
136.2TF
252.8TF
0MWM
218TF
190TF
0AMH01 0218
128.5TF
235.1TF
325.5MGOCONNECTION AT THE MH 9 OC'LOCK
71.3TF

Properties (7)

additional_info
630074090221201
custom_field_three
AGGREGATE VISIBLE/CRACKS/FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-09-02T23:30:34-07:00
documentation
PROPIPE
is_lateral_inspection
false