Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2021, 07:27 AM
  • 01 0213_01 0212_09032021_004223.mp4

Date
09/03/2021
W/O
911861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01255
Time
12:27 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9348
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_911861_TV01011_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0213
Downstream MH
01 0212
Dir. of Survey
Downstream
Length Surveyed
305 ft.
Total Length
305 ft.
Structural Index
3
Structural Quick
433L
Structural Rating
201
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
201
Pipe schematic from manhole 01 0213 to 01 0212
MH: 01 0213MH: 01 0212downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02130 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"108.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.5 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES182.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"187.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.8 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES227.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"268.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"269.2 ft. FS - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES282 ft. FM - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES287.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES299.1 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES305 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish305 ft. AMH - Downstream Manhole, Survey Ends - 01 0212305 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (7)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    176.5 ft. - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    198.8 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

    269.2 ft. - Fracture Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

    282 ft. - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    287.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    299.1 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
187.2TF
197.5TF
176.5FM
0AMH01 0213
268.2TF
299.1FM
2.8SAV
265.6TF
227.5TF
108.2TF
0MWM
269.2FS
305SAV
0MWL
305AMH01 0212
22.4TF
282FM
198.8FS
93.9TF
182.1TF
143.8TF
37.3TF
148.6TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
305MGOCONNECTION AT THE MH 9 OC'LOCK
287.1FL

Properties (7)

additional_info
630074090221201
custom_field_three
AGGREGATE VISIBLE/FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-09-03T00:27:42-07:00
documentation
PROPIPE
is_lateral_inspection
false