Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2021, 09:42 AM
  • 01 0211_01 0210_09102021_030601.mp4

Date
09/10/2021
W/O
911861
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00202
PipeID
P01253
Time
2:42 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9127
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_911861_TV01011_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0211
Downstream MH
01 0210
Dir. of Survey
Downstream
Length Surveyed
345.9 ft.
Total Length
345.9 ft.
Structural Index
3
Structural Quick
413M
Structural Rating
211
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
215
Pipe schematic from manhole 01 0211 to 01 0210
MH: 01 0211MH: 01 0210downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02110 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start62.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"72.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"77 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"114.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"121 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"153.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"159.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"190.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"194.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"204.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"208 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES239.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"274.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"279.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"312.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"319.2 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES342.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish345.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK345.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0210

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    208 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    319.2 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
342.9SAV
0AMH01 0211
194.2TF
159.3TF
190.7TF
2SAV
345.9MGOCONNECTION AT THE MH 9 OC'LOCK
121TFA
274.8TF
153.9TF
0MWL
312.5TF
0MWM
72.3TF
345.9AMH01 0210
62.4TF
319.2CM
279.9TF
239.4TF
208FM
114.1TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
77TF
204.5TF

Properties (6)

custom_field_three
AGGREGATE VISIBLE/FRACTURES
custom_field_two
3
customer
1
datetime
2021-09-10T02:42:40-07:00
documentation
PROPIPE
is_lateral_inspection
false