Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2021, 10:07 AM
  • 01 0210_01 0209_09102021_033042.mp4

Date
09/10/2021
W/O
911861
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00202
PipeID
P01252
Time
3:07 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9127
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_911861_TV01011_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0210
Downstream MH
01 0209
Dir. of Survey
Downstream
Length Surveyed
348.6 ft.
Total Length
348.6 ft.
Structural Index
3
Structural Quick
413M
Structural Rating
214
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
218
Pipe schematic from manhole 01 0210 to 01 0209
MH: 01 0210MH: 01 0209downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02100 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"13.3 ft. FS - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES45.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"53.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"86.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"106.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"129.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"152.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"167.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"190.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"211 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"228.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"251.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"271.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"292 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8" - COLLAPSED314.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"325.9 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES329.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"345.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0209348.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

    13.3 ft. - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    325.9 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
292TFCOLLAPSED
129.4TF
152.2TF
53.1TF
314.5TF
0MWL
7.4TF
345.8SAP
2SAP
167.5TF
190.1TF
348.6AMH01 0209
329.6TF
211TF
0MWM
228.5TF
0AMH01 0210
325.9FM
13.3FS
106.6TF
86.3TF
348.6MGOCONNECTION AT THE MH 9 OC'LOCK
251.2TF
45.7TF
271.4TF
0MGOCONNECTION AT THE MH 9 OC'LOCK

Properties (6)

custom_field_three
AGGREGATE PROJECTING/FRACTURES
custom_field_two
3
customer
1
datetime
2021-09-10T03:07:43-07:00
documentation
PROPIPE
is_lateral_inspection
false