Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2021, 05:34 AM
  • H 0477_H 0476_09082021_225813.mp4

Date
09/08/2021
W/O
911489
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00178
PipeID
P21377
Time
10:34 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9351
Sewer Name
H JOINT OUTFALL H - UNIT 5B
City
AVOCADO HEIGHTS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_911489_TV15211_SEP2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0477
Downstream MH
H 0476
Dir. of Survey
Downstream
Length Surveyed
445.9 ft.
Total Length
445.9 ft.
Structural Index
4
Structural Quick
5P3Q
Structural Rating
679
O&M Index
2
O&M Quick
2Q00
O&M Rating
176
Overall Index
3
Overall Quick
Overall Rating
855
Pipe schematic from manhole H 0477 to H 0476
MH: H 0477MH: H 0476downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 04770 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"25.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start72.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"310.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6" - POSSIBLY A SMALL OUTLET PIPE (ACTIVE) / FITTING @ INNER WALL OF TAP.442.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish442.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish442.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish445 ft. MGO - General Observation - COCKROACHES IN MANHOLE445 ft. MGO - General Observation - CONNECTION AT MH 2 O'CLOCK445.9 ft. AMH - Downstream Manhole, Survey Ends - H 0476

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    8 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    25.6 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    445 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
74.5TFA
8TFA
0MWM
0AMHH 0477
442.6DAGS
2SAP
442.6SRV
25.6SRV
442.6SAP
72.7TFC
445MGOCOCKROACHES IN MANHOLE
175.6TFA
445.9AMHH 0476
0MWL
2DAGS
242.2TFA
310.8TBAPOSSIBLY A SMALL OUTLET PIPE (ACTIVE) / FITTING @ INNER WALL OF TAP.
445MGOCONNECTION AT MH 2 O'CLOCK

Properties (7)

additional_info
630069090821201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-09-08T22:34:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false