Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2021, 08:27 AM
  • 14 1106_14 1105_08312021_014000.mp4

Date
08/31/2021
W/O
911390
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26058
Time
1:27 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9250
Sewer Name
14 WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_911390_TV14056_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 1106
Downstream MH
14 1105
Dir. of Survey
Downstream
Length Surveyed
335 ft.
Total Length
335 ft.
Structural Index
2
Structural Quick
2L00
Structural Rating
132
O&M Index
2
O&M Quick
2Y00
O&M Rating
264
Overall Index
2
Overall Quick
Overall Rating
396
Pipe schematic from manhole 14 1106 to 14 1105
MH: 14 1106MH: 14 1105downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 11060 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start68.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN119.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN123.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN171.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6" - OPEN215.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN219.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN267.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN315.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN319.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN333 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish333.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish335 ft. AMH - Downstream Manhole, Survey Ends - 14 1105

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
333SSS
119.3TFOPEN
171.5TFOPEN
215.1TFOPEN
219.1TFOPEN
315.7TFOPEN
2DAGS
333.3DAGS
267.2TFOPEN
0MWL
335AMH14 1105
2SSS
123.9TFOPEN
0AMH14 1106
2DAE
68.1TFOPEN
319.6TFOPEN
0MWM
333.3DAE

Properties (8)

additional_info
630069083021201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-08-31T01:27:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40175