Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 27, 2021, 07:29 AM
  • 14 1123_14 1122_08272021_003814.mp4

Date
08/27/2021
W/O
911390
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26075
Time
12:29 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9246
Sewer Name
14 WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_911390_TV14056_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 1123
Downstream MH
14 1122
Dir. of Survey
Downstream
Length Surveyed
305 ft.
Total Length
305 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2W00
O&M Rating
240
Overall Index
2
Overall Quick
Overall Rating
240
Pipe schematic from manhole 14 1123 to 14 1122
MH: 14 1123MH: 14 1122downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 11232 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start11.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN154.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN302.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish302.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish305 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/305 ft. AMH - Downstream Manhole, Survey Ends - 14 1122

Observation photos (1)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
302.7DAGS
0MWL
11.3TFOPEN
0MWM
0AMH14 1123
2DAGS
302.7DAE
2DAE
305MGOCONN @ MH 3 O'CLOCK/
305AMH14 1122
154.1TFOPEN

Properties (8)

additional_info
630069082621201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-08-27T00:29:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40175