Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 13, 2021, 05:20 AM
  • 32 1169_32 1168_08122021_223321.mp4

Date
08/12/2021
W/O
906609
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00839
PipeID
P19623
Time
10:20 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9234
Sewer Name
32 SAN FERNANDO ROAD TRUNK
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_906609_TV32021_AUG2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1169
Downstream MH
32 1168
Dir. of Survey
Downstream
Length Surveyed
405.3 ft.
Total Length
405.3 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
398
O&M Index
2
O&M Quick
312O
O&M Rating
163
Overall Index
2
Overall Quick
Overall Rating
561
Pipe schematic from manhole 32 1169 to 32 1168
MH: 32 1169MH: 32 1168downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 11690 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"58.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.9 ft. RMJ - Roots Medium Joint, from 04 to 08 o'clock, 10 %, within 8 inches of joint: YESR225 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"403.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish403.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish403.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405.3 ft. AMH - Downstream Manhole, Survey Ends - 32 1168405.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 04 to 08 o'clock, 10 %, within 8 inches of joint: YESR

    96.9 ft. - Roots Medium Joint, from 04 to 08 o'clock, 10 %, within 8 inches of joint: YESR

Observations (16)

DistanceCodeObservation
2DAGS
405.3AMH32 1168
38.3TFC
0AMH32 1169
6.8SSS
405.3MGOCONNECTION AT MH 3 O'CLOCK
96.9RMJ
2SAP
58.8TFC
403.1SAP
403.1DAGS
228.5TFC
0MWM
403.1SSS
225TFA
0MWL

Properties (7)

additional_info
630069081221202
custom_field_three
PROJECTING AGGREGATE/SPALLING
custom_field_two
2
customer
1
datetime
2021-08-12T22:20:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false