Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2021, 06:09 AM
  • 08 0621_08 0620_09132021_232145.mp4

Date
09/13/2021
W/O
911336
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00008
PipeID
P00660
Time
11:09 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9405
Sewer Name
08 GRACE STREET RELIEF TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_911336_TV08018_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
08 0621
Downstream MH
08 0620
Dir. of Survey
Downstream
Length Surveyed
390.4 ft.
Total Length
390.4 ft.
Structural Index
2
Structural Quick
312^
Structural Rating
313
O&M Index
2
O&M Quick
2N00
O&M Rating
154
Overall Index
2
Overall Quick
Overall Rating
467
Pipe schematic from manhole 08 0621 to 08 0620
MH: 08 0621MH: 08 0620downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 06212 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start245.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES251.7 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES388 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish388 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish388 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Finish390.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0620

Observation photos (2)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    245.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    251.7 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
2MWLS
251.7FL
2SSS
0MWL
390.4AMH08 0620
388DAGS
245.4CL
388SSS
0MGOROACHES @ MH
388MWLS
2DAGS
0MWM
0AMH08 0621

Properties (8)

additional_info
630074091321201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-09-13T23:09:05-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
30636