Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2021, 11:50 AM
  • 08 0614_08 0001_09132021_045354.mp4

Date
09/13/2021
W/O
911336
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00008
PipeID
P00653
Time
4:50 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9404
Sewer Name
08 GRACE STREET RELIEF TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_911336_TV08018_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
08 0614
Downstream MH
08 0001
Dir. of Survey
Downstream
Length Surveyed
29 ft.
Total Length
29 ft.
Structural Index
2
Structural Quick
2500
Structural Rating
10
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
20
Pipe schematic from manhole 08 0614 to 08 0001
MH: 08 0614MH: 08 0001downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 06140 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish26 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish29 ft. AMH - Downstream Manhole, Survey Ends - 08 0001 ZOOMED IN

Observation photos (1)

  • Downstream Manhole, Survey Ends - 08 0001 ZOOMED IN

    29 ft. - Downstream Manhole, Survey Ends - 08 0001 ZOOMED IN

Observations (8)

DistanceCodeObservation
0AMH08 0614
0MWM
2DAGS
0MWL
2SSS
26DAGS
26SSS
29AMH08 0001 ZOOMED IN

Properties (8)

additional_info
630074091321003
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-09-13T04:50:16-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
30636