Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2021, 08:45 AM
  • 22 0880_22 0879_09132021_015610.mp4

Date
09/13/2021
W/O
911293
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00798
PipeID
P17249
Time
1:45 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9359
Sewer Name
22 CONEY TRUNK, SECTION 1
City
AZUSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
WO_911293_TV22132_SEP2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0880
Downstream MH
22 0879
Dir. of Survey
Downstream
Length Surveyed
333.5 ft.
Total Length
333.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 22 0880 to 22 0879
MH: 22 0880MH: 22 0879downstream0 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 08800 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT69.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"101 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"165.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"332 ft. MGO - General Observation - Surface Spalling throughout the reach, from 9 to 3 o'clock333.5 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK333.5 ft. AMH - Downstream Manhole, Survey Ends - 22 0879

Observation photos (1)

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

Observations (14)

DistanceCodeObservation
197.7TBA
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0AMH22 0880
333.5MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
245.9TBA
332MGOSurface Spalling throughout the reach, from 9 to 3 o'clock
0MWM
333.5AMH22 0879
165.1TBA
101TBA
69.1TFC
2MGOMAG COATING THROUGHOUT
286.9TF
0MWL

Properties (6)

additional_info
630069091321001
custom_field_two
3
customer
1
datetime
2021-09-13T01:45:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false