Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2021, 06:21 AM
  • H 0230_H 0229_08242021_233215.mp4

Date
08/24/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10647
Time
11:21 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9244
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0229
Downstream MH
H 0230
Dir. of Survey
Upstream
Length Surveyed
329.3 ft.
Total Length
329.3 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole H 0229 to H 0230
MH: H 0229MH: H 0230upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - H 02302.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish97.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"200.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"284 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start299.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start329.3 ft. MWL - Water Level, 5 %of cross sectional area329.3 ft. MWL - Water Level, 10 %of cross sectional area329.3 ft. AMH - Downstream Manhole, Survey Begins - H 0229329.3 ft. MWM - Water Mark, 15 %of cross sectional area329.3 ft. MWM - Water Mark, 15 %of cross sectional area329.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK329.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • Water Mark, 15 %of cross sectional area

    0 ft. - Water Mark, 15 %of cross sectional area

  • Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    30.2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    45.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    329.3 ft. - General Observation - COCKROACHES IN MANHOLE

  • Upstream Manhole, Survey Ends - H 0230

    329.3 ft. - Upstream Manhole, Survey Ends - H 0230

Observations (15)

DistanceCodeObservation
0MWL
0MWL
0AMHH 0229
0MWM
45.3CM
232TFC
0MWM
30.2DAGS
128.5TFC
0MGOCONNECTION AT MH 9 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
327.1DAGS
327.1CM
329.3MGOCOCKROACHES IN MANHOLE
329.3AMHH 0230

Properties (7)

additional_info
630069082421201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-08-24T23:21:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false