Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2021, 05:29 AM
  • H 0226_H 0225_08242021_230101.mp4

Date
08/24/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10643
Time
10:29 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9244
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0226
Downstream MH
H 0225
Dir. of Survey
Downstream
Length Surveyed
289.7 ft.
Total Length
289.7 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
126
O&M Index
2
O&M Quick
3J2K
O&M Rating
280
Overall Index
3
Overall Quick
Overall Rating
406
Pipe schematic from manhole H 0226 to H 0225
MH: H 0226MH: H 0225downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 02260 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start22.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS UNDER WATER33.5 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: NO, 6", 2"80.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start86.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"190.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"289.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish289.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish289.7 ft. MSA - Survey Abandoned - NEED REVERSAL FROM D/S MH.289.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
86.1TFC
289.7CM
0AMHH 0226
0MWM
289.7DAGS
0MGOCOCKROACHES IN MANHOLE
22.1DSZDEBRIS UNDER WATER
289.7MSANEED REVERSAL FROM D/S MH.
80.5CM
33.5TBI
190.9TFC
289.7DSZ
2DAGS

Properties (7)

additional_info
630069082421201
custom_field_three
CRACKS/DEBRIS
custom_field_two
3
customer
1
datetime
2021-08-24T22:29:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false