Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2021, 07:21 AM
  • H 0226_H 0225_08252021_002542.mp4

Date
08/25/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10643
Time
12:21 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9244
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0225
Downstream MH
H 0226
Dir. of Survey
Upstream
Length Surveyed
40.3 ft.
Total Length
40.3 ft.
Structural Index
3
Structural Quick
3700
Structural Rating
21
O&M Index
2
O&M Quick
2A00
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
41
Pipe schematic from manhole H 0225 to H 0226
MH: H 0225MH: H 0226upstream0 ft. MSA - Survey Abandoned - REVERSAL COMPLETE.0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"8 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start36.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start40.3 ft. AMH - Downstream Manhole, Survey Begins - H 022540.3 ft. MWL - Water Level, 15 %of cross sectional area40.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE40.3 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
37.5TFC
40.3MSAREVERSAL COMPLETE.
2DAGS
0AMHH 0225
3.8CM
0MWL
0MGOCOCKROACHES IN MANHOLE
0MWM
40.3CM
40.3DAGS
40.3DSZ
32.3DSZ

Properties (7)

additional_info
630069082421201
custom_field_three
CRACKS/DEBRIS
custom_field_two
3
customer
1
datetime
2021-08-25T00:21:01-07:00
documentation
PRO PIPE
is_lateral_inspection
false