Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2021, 07:07 AM
  • H 0225_H 0224_08252021_002033.mp4

Date
08/25/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10642
Time
12:07 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9244
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0224
Downstream MH
H 0225
Dir. of Survey
Upstream
Length Surveyed
328.9 ft.
Total Length
328.9 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
141
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
271
Pipe schematic from manhole H 0224 to H 0225
MH: H 0224MH: H 0225upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 02250 ft. MGO - General Observation - COCKROACHES IN MANHOLE2.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish55.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"159.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"235.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start255.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"326.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start328.9 ft. MWM - Water Mark, 15 %of cross sectional area328.9 ft. MWL - Water Level, 5 %of cross sectional area328.9 ft. AMH - Downstream Manhole, Survey Begins - H 0224

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    93.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    328.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
169.7TFC
0MWM
2DAGS
328.9AMHH 0225
273.4TFC
73TFC
326.4CM
328.9MGOCOCKROACHES IN MANHOLE
93.7CM
326.4DAGS
0MWL
0AMHH 0224

Properties (7)

additional_info
630069082421201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-08-25T00:07:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false