Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2021, 07:45 AM
  • H 0223_H 0222_08252021_005645.mp4

Date
08/25/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10640
Time
12:45 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9244
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0223
Downstream MH
H 0222
Dir. of Survey
Downstream
Length Surveyed
332.2 ft.
Total Length
332.2 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
307
Pipe schematic from manhole H 0223 to H 0222
MH: H 0223MH: H 0222downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 02230 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start32.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start73 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"172.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"270.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"329.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish329.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish332.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE332.2 ft. AMH - Downstream Manhole, Survey Ends - H 0222

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    32.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    332.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
2DAGS
0MGOCOCKROACHES IN MANHOLE
332.2MGOCOCKROACHES IN MANHOLE
270.1TFC
0AMHH 0223
329.1DAGS
73TFC
172.8TFC
0MWL
32.3CM
0MGOCONNECTION AT MH 3 O'CLOCK
332.2AMHH 0222
0MWM
329.1CM

Properties (7)

additional_info
630069082421201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-08-25T00:45:49-07:00
documentation
PRO PIPE
is_lateral_inspection
false