Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2021, 08:59 AM
  • H 0232_H 0231A_08242021_020820.mp4

Date
08/24/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10650
Time
1:59 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9243
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0231A
Downstream MH
H 0232
Dir. of Survey
Upstream
Length Surveyed
334 ft.
Total Length
334 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
132
Pipe schematic from manhole H 0231A to H 0232
MH: H 0231AMH: H 0232upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - H 02322.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish82.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"183.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"286 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"332 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start334 ft. MWM - Water Mark, 10 %of cross sectional area334 ft. AMH - Downstream Manhole, Survey Begins - H 0231A334 ft. MGO - General Observation - COCKROACHES IN MANHOLE334 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    334 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
150.7TFC
0MWM
334MGOCOCKROACHES IN MANHOLE
331.2DAGS
251.5TFC
334MGOCONNECTION AT MH 9 O'CLOCK
0AMHH 0231A
2DAGS
48TF
0MGOCOCKROACHES IN MANHOLE
334AMHH 0232
0MWL

Properties (7)

additional_info
630069082321201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-08-24T01:59:41-07:00
documentation
PRO PIPE
is_lateral_inspection
false