Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2021, 09:34 AM
  • H 0231_H 0230_08242021_024757.mp4

Date
08/24/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10648
Time
2:34 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9243
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0231
Downstream MH
H 0230
Dir. of Survey
Downstream
Length Surveyed
335.9 ft.
Total Length
335.9 ft.
Structural Index
3
Structural Quick
3C21
Structural Rating
68
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
216
Pipe schematic from manhole H 0231 to H 0230
MH: H 0231MH: H 0230downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 02310 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start21.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"26.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES122.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"206.2 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start220.5 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES221.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"232.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES235.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start247.8 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish322.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"334 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish334 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish335.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE335.9 ft. AMH - Downstream Manhole, Survey Ends - H 0230

Observation photos (8)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    26.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Settled Fine,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    206.2 ft. - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    220.5 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    232.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    235.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    335.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
232.1CL
21.1TFC
0MWM
322.9TFC
206.2DSF
0MGOCONNECTION AT MH 3 O'CLOCK
2DAGS
0AMHH 0231
235.4CM
335.9MGOCOCKROACHES IN MANHOLE
220.5CM
26.3CM
0MGOCOCKROACHES IN MANHOLE
247.8DSF
0MWL
334CM
122.8TFC
334DAGS
221.3TFC
335.9AMHH 0230

Properties (7)

additional_info
630069082321201
custom_field_three
MULTIPLE CRACKS/SETTLED DEPOSITS
custom_field_two
3
customer
1
datetime
2021-08-24T02:34:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false