Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2021, 04:51 AM
  • H 0261_H 0260_08192021_220334.mp4

Date
08/19/2021
W/O
906511
Weather
Dry
Operator/Surveyor
S, LOPEZ
Sewer ID
Z00171
PipeID
P10684
Time
9:51 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9241
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
VERNON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_906511_TV02170_AUG2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0261
Downstream MH
H 0260
Dir. of Survey
Downstream
Length Surveyed
363 ft.
Total Length
363 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
146
Pipe schematic from manhole H 0261 to H 0260
MH: H 0261MH: H 0260downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - H 02610 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start81.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"186.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"186.5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES253.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"277 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"286.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"360.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish363 ft. AMH - Downstream Manhole, Survey Ends - H 0260363 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    186.5 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    363 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
253.2TFA
363AMHH 0260
0MGOCOCKROACHES IN MANHOLE
81.2TFC
186.5TFC
179.7TFC
88.7TFC
360.1DAGS
0AMHH 0261
186.5CL
277TF
363MGOCOCKROACHES IN MANHOLE
0MWM
0MWL
2DAGS
286.5TFC

Properties (7)

additional_info
630069081921201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-08-19T21:51:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false